10/100M to 2-port RS-485/422 Serial Port Server
Manufacturer Part Number: HESS-T-011
Brand: Predision
$ 191.00
- 2 x RS-485/422 Port + 1 x 10/100M Port
- Metal Housing, Din-rail or Wall Mounted
- WorkingTemperature: -40 ~ 85°C
- Wide Power Input: 12 ~ 57.6 VDC
- Baud Rate: 300 - 921,600 bps
- Supports Multiple Operation Modes: VCOM, MCP, TCP SERVER, TCP CLIENT, UDP,Remote Pair Mode, Modbus TCP SERVER, Modbus TCP CLIENT
- Supports Web Firmware Upgrade
See our Shipping Policy for delivery regions and fees
HESS-T-011 serial device server provides a serial to network function that converts RS-485/422 serial ports into TCP/IP network interfaces, enabling transparent bi-directional data transmission between RS-485/422 serial ports and TCP/IP network interfaces.
Hardware
| CPU | 32-bit LX6 240 MHZ Microprocessor |
| RAM | 520K |
| Ethernet Interface | 10/100M (Embedded 1.5KV Electromagnetic isolation) Adaptive MDI/MDI-XEthernet Interface, Interface Mode RJ45 |
| Serial Port | RS-232/485/422 three-in-one or RS-485/422 |
| Serial Interface | 4-pin 3.81 Plug-in Terminal |
| Indicator Light | Power Indicator Light: PWR, Running Indicator Light: RUN, Serial Port 1 and Serial Port 2 Transmit and Receive Indicator: T/R1, T/R2 |
| Power Interface | DC-005 DC Socket or 3-pin 5.08 Terminal Power Supply Mode, Built-in Anti-reverse Connection Protection |
| Power Range | DC 12~57.6V |
| Function Buttons | 1 Factory Reset Button RESET |
| Max. Power Consumption | 12 V @ 150 mA |
| Housing | Metal Housing, with IP30 Protection Level |
| Installation | Din-rail or Wall Mounted |
| Operating Environment | Storage Temperature: -40~85°C Operating Temperature: -40~85°C Relative Humidity: 5~95% (Non-condensing) |
| Altitude | 0~4000m |
| Dimensions L×W×H | 100 ×80.8 ×30 mm (Excluding Mounting Parts) |
| Net. Weight | 248g |
Software
| Protocol Support | ARP, IP, ICMP, UDP, TCP, HTTP, DHCP, MODBUS |
| Configuration Method | Web Browser, VCOM Utility (Virtual COM Only Windows) |
| Operating Mode | VCOM, MCP, TCP SERVER, TCP CLIENT, UDP, Modbus TCP SERVER, Modbus TCP CLIENT |
| Baud Rate | 300 - 921,600 bps |
| Data Bits | 5, 6, 7, 8 |
| Stop Bits | 1, 2 |
| Check Bits | None, Odd, Even |
Industrial Standard
| EMC | 55032/24 |
| EMI | CISPR 32, FCC Part 15B Class A |
| EMS | IEC61000-4-2 ESD: Contact 6kV, Air 8kV IEC61000-4-3 RS: 80 MHz-1 GHz 3V/m IEC61000-4-4 EFT: Power 1kV, Signal0.5kV IEC61000-4-5 Surge: Power Differential Mode 1KV, Common Mode 2KV (8/20); Ethernet Ports Differential Mode 1KV, Common Mode 2KV (10/700 us); RS-232/485/422 Differential Mode 1KV, Common Mode 2KV (10/700 us) IEC61000-4-6 CS: 150 KHz-80 MHz 3V/m |
2-channel Isolated RS-485/422 + 1 Channel 10/100M Port, Din-rail, DC 12~36V, Baud Rate 300-921,600 bps
2 × RS-232/485/422 Port + 1 × 10/100M Port, Din-rail, DC12 ~ 48V, Metal Housing, Baud Rate 300-921,600 bps
2-channel RS-485/422 + 1 Channel 10/100M Port, Din-rail, DC 12V~57.6V, Baud Rate 300-921,600 bps
5-Year Warranty
24/7 Live Service
Global Support
Partner Privileges
OEM/ODM Available
Company Information
Contact Us
Our Address
11 Commerce St.
Norwalk, CT 06850
United States
Sign up for Our Newsletter
Career Opportunities
We make every effort to create a fair and productive workplace.
See our latest openings below!
Information & News
Shop With Confidence
Shop with the top ranking
payment platform
We accept Visa, Mastercard, American Express, Paypal, Company Purchase Orders
We're Here to Help!
Contact us and we'll get you to the right person as soon as possible!








Copyright © 2013-2026 Predision LLC. All Rights Reserved
Predision LLC - Authorized distributor of Henrich Electronics industrial Ethernet & IoT connectivity solutions